Boiler leaking, any idea how to sort it?

£0.00 @
Just noticed water leaking out of my boiler Baxi 60/100, i've opened the front and there is water dripping from this thing (see photos) Any idea whats causing it and how to sort it? Read More
steevieboy4u Avatar
4m, 4w agoPosted 4 months, 4 weeks ago
Just noticed water leaking out of my boiler Baxi 60/100, i've opened the front and there is water dripping from this thing (see photos)
Any idea whats causing it and how to sort it?
Tags:
steevieboy4u Avatar
4m, 4w agoPosted 4 months, 4 weeks ago
Options
Best Answer
Hi, my names Matt i own EM-Gas & Heating,
check out this link that im about to send, it shows how to change the central heating differential valve,

http://www.acwilgar.co.uk/Boiler-Manual-PDF/Baxi/System%2035-60%20&%2060-100.pdf

check section 12.

All Responses

(23) Jump to unreadPost an answer
Responses/page:
#1
photos?
#3
Burst Seal?
#4
Have the photos uploaded ok, trying to do all this on my phone and its proving more difficult than I thought :P
#5
It looks like it's coming from some kind of metal push pin
#6
Hi, my names Matt i own EM-Gas & Heating,
check out this link that im about to send, it shows how to change the central heating differential valve,

http://www.acwilgar.co.uk/Boiler-Manual-PDF/Baxi/System%2035-60%20&%2060-100.pdf

check section 12.
#7
you can buy a servicing kit which will include a diaphram washer, which will have split which is why it is leaking
#8
OP's photo's
http://i128.photobucket.com/albums/p199/steevieboy4u/Public%20Images/IMG_20161129_203901_zpsvmrosbsc.jpg
http://i128.photobucket.com/albums/p199/steevieboy4u/Public%20Images/IMG_20161129_204518_zpsqzvh9beq.jpg
http://i128.photobucket.com/albums/p199/steevieboy4u/Public%20Images/IMG_20161129_203423_zpsm5wk6ob4.jpg
http://i128.photobucket.com/albums/p199/steevieboy4u/Public%20Images/IMG_20161129_203415_zps5hvtklos.jpg


Edited By: philphil61 on Nov 29, 2016 21:20
#9
if its stuck in, grab it with some plyers, and get some grease and pull it in and out it might free it up
#10
mbordacs
you can buy a servicing kit which will include a diaphram washer, which will have split which is why it is leaking


That's great and I reckon that's exactly what's wrong, can I do it myself or does a gas safe eng need to do it?

The info mentions about draining the primary circuit? :P
#11
mbordacs
if its stuck in, grab it with some plyers, and get some grease and pull it in and out it might free it up


Is it safe to remove the micro switch? Or do I need to isolate the power
#12
steevieboy4u
mbordacs
if its stuck in, grab it with some plyers, and get some grease and pull it in and out it might free it up


Is it safe to remove the micro switch? Or do I need to isolate the power


Isolate all mains when working as electric and water tend not to mix well.
#13
Yeah better safe than sorry
#14
Argh! stupid thing tried pulling the pin out and because there was hardly anything to grab hold of its pushed it in and it's not coming out now!
It's not leaking anymore though.
What does it do when it's pushed in?
#15
Turn off the power and cold water feed, remove the screw and move the switch out of the way to expose the pin, undo the brass nut which the pin sticks out of, and you will find a small rubber washer around the base of the pin, you need to replace it, you can get a kit which usually includes a diaphragm, a washer, and a new brass nut with a larger metal washer, you probably won't need to replace the diaphragm, just the small washer and the nut/metal washer
#16
mikey_d
Turn off the power and cold water feed, remove the screw and move the switch out of the way to expose the pin, undo the brass nut which the pin sticks out of, and you will find a small rubber washer around the base of the pin, you need to replace it, you can get a kit which usually includes a diaphragm, a washer, and a new brass nut with a larger metal washer, you probably won't need to replace the diaphragm, just the small washer and the nut/metal washer


The cold water feed is that the 2 black valves at the bottom of the boiler that turn 90 degrees?
If I undo the brass nut around the pin will water come out?
Cheers
#17
steevieboy4u
mikey_d
Turn off the power and cold water feed, remove the screw and move the switch out of the way to expose the pin, undo the brass nut which the pin sticks out of, and you will find a small rubber washer around the base of the pin, you need to replace it, you can get a kit which usually includes a diaphragm, a washer, and a new brass nut with a larger metal washer, you probably won't need to replace the diaphragm, just the small washer and the nut/metal washer
The cold water feed is that the 2 black valves at the bottom of the boiler that turn 90 degrees?
If I undo the brass nut around the pin will water come out?
Cheers
No, they sound like the central heating valves, if you haven't got an isolator valve you may need to turn off the main stopcock into the house. Once the water feed is off, turn on the hot tap to let out any water in the pipes, and you only get a dribble when you remove the nut, a possible temporary fix is to remove the small washer. dry it off, smear it with silicon grease, and reassemble, but it is better to replace it, I have a baxi 105 and I have had to do this every couple of years
#18
mikey_d
steevieboy4u
mikey_d
Turn off the power and cold water feed, remove the screw and move the switch out of the way to expose the pin, undo the brass nut which the pin sticks out of, and you will find a small rubber washer around the base of the pin, you need to replace it, you can get a kit which usually includes a diaphragm, a washer, and a new brass nut with a larger metal washer, you probably won't need to replace the diaphragm, just the small washer and the nut/metal washer
The cold water feed is that the 2 black valves at the bottom of the boiler that turn 90 degrees?
If I undo the brass nut around the pin will water come out?
Cheers
No, they sound like the central heating valves, if you haven't got an isolator valve you may need to turn off the main stopcock into the house. Once the water feed is off, turn on the hot tap to let out any water in the pipes, and you only get a dribble when you remove the nut, a possible temporary fix is to remove the small washer. dry it off, smear it with silicon grease, and reassemble, but it is better to replace it, I have a baxi 105 and I have had to do this every couple of years


It'll have to be the mains stop tap I use then.

I'll have a mess tomorrow as i've got to be up at 5am for work, so i'm off to bed now.

Thanks for all the advice & help I really appreciate it
#19
mbordacs
you can buy a servicing kit which will include a diaphram washer, which will have split which is why it is leaking


Thanks for all the advice & help I really appreciate it
#20
mikey_d
steevieboy4u
mikey_d
Turn off the power and cold water feed, remove the screw and move the switch out of the way to expose the pin, undo the brass nut which the pin sticks out of, and you will find a small rubber washer around the base of the pin, you need to replace it, you can get a kit which usually includes a diaphragm, a washer, and a new brass nut with a larger metal washer, you probably won't need to replace the diaphragm, just the small washer and the nut/metal washer
The cold water feed is that the 2 black valves at the bottom of the boiler that turn 90 degrees?
If I undo the brass nut around the pin will water come out?
Cheers
No, they sound like the central heating valves, if you haven't got an isolator valve you may need to turn off the main stopcock into the house. Once the water feed is off, turn on the hot tap to let out any water in the pipes, and you only get a dribble when you remove the nut, a possible temporary fix is to remove the small washer. dry it off, smear it with silicon grease, and reassemble, but it is better to replace it, I have a baxi 105 and I have had to do this every couple of years


its not a combi its a system boiler, its not for hot water, its central heating
#21
there is only 2 pipes going to this boiler, flow and return, turn them both off underneath and get some bog roll and catch the water tht comes out when you undo the front
#22
mbordacs
there is only 2 pipes going to this boiler, flow and return, turn them both off underneath and get some bog roll and catch the water tht comes out when you undo the front

Yes thats right - It's a system boiler.

Cheers will have a bash when i get home from work tonight.

Just another quick question, roughly how far should this pin be sticking out as i'm assuming it must be over 5mm for it to activate the micro switch?
#23
Just a quick update. Boiler all sorted, it was just a matter of taking the brass nut out cleaning it up where the pin was located and putting some silicon grease on. No more leaking and central heating and hot water restored :)

Thanks again mbordacs and mikey_d

Post an Answer

You don't need an account to leave a response. Just enter your email address. We'll keep it private.

...OR log in with your social account

...OR comment using your social account

Thanks for your comment! Keep it up!
We just need to have a quick look and it will be live soon.
The community is happy to hear your opinion! Keep contributing!