Gas fire hearth advice

£0.00 @
Are there any gas fitters here who can advise on the legal requirements for a hearth for our gas fire. The fire is wall mounted and the bottom of it is 60mm above a carpeted concrete floor, bottom … Read More
spoo Avatar
2m, 1w agoPosted 2 months, 1 week ago
Are there any gas fitters here who can advise on the legal requirements for a hearth for our gas fire.

The fire is wall mounted and the bottom of it is 60mm above a carpeted concrete floor, bottom of the gas burners is around 200mm from the floor but hard to say for sure. I'm pretty confident I need a hearth which extends 12 inches to the front and 6 inches to each side of the fire but don't know how thick it needs to be, google is giving me contradictory info.
Tags:
spoo Avatar
2m, 1w agoPosted 2 months, 1 week ago
Options
Best Answer
225mm minimum at the front and 150mm minimum at the side. hearth 12mm thick minimum, not all gas fires require a hearth, check your gas fire instructions. see building regs document j paragraph 3.4, download it for free online it tells you all you need to know.

All Responses

(6) Jump to unreadPost an answer
Responses/page:
#1
225mm minimum at the front and 150mm minimum at the side. hearth 12mm thick minimum, not all gas fires require a hearth, check your gas fire instructions. see building regs document j paragraph 3.4, download it for free online it tells you all you need to know.
#2
matthews9479
225mm minimum at the front and 150mm minimum at the side. hearth 12mm thick minimum, not all gas fires require a hearth, check your gas fire instructions. see building regs document j paragraph 3.4, download it for free online it tells you all you need to know.

Thanks, have just looked at the regs, all looks fairly clear. We don't have the instructions for the fire, it came with the house when my partner bought it 15 years ago.
#3
spoo
matthews9479
225mm minimum at the front and 150mm minimum at the side. hearth 12mm thick minimum, not all gas fires require a hearth, check your gas fire instructions. see building regs document j paragraph 3.4, download it for free online it tells you all you need to know.

Thanks, have just looked at the regs, all looks fairly clear. We don't have the instructions for the fire, it came with the house when my partner bought it 15 years ago.


so have u been using it for 15 years then if nothings gone wrong it's probably all good.
#4
MynameisM

so have u been using it for 15 years then if nothings gone wrong it's probably all good.

It probably is, the reason for getting a hearth is we'll be moving house later in the year and I think for the type of fire we have a hearth is now a legal requirement, it looks a little like this one: http://www.daveanderson.org.uk/photos/gasfire.jpg

If I've got it wrong and we don't need one after all that's great, it'll save us a few quid but I think the fact it's only 60mm above the floor means it should really have one.



Edited By: spoo on Feb 19, 2017 21:55
#5
spoo
MynameisM

so have u been using it for 15 years then if nothings gone wrong it's probably all good.

It probably is, the reason for getting a hearth is we'll be moving house later in the year and I think for the type of fire we have a hearth is now a legal requirement, it looks a little like this one: http://www.daveanderson.org.uk/photos/gasfire.jpg

If I've got it wrong and we don't need one after all that's great, it'll save us a few quid but I think the fact it's only 60mm above the floor means it should really have one.




so u mean like for tenants when they move in to ur house then I see. these regs seem pointless if it's ur own house it's fine no annual gas checks etc but for tenants it all needs be done.
#6
You should still have all appliances checked and serviced yearly whatever the situation.
If there was an issue your gas engineer should have flagged it up to you.

Post an Answer

You don't need an account to leave a response. Just enter your email address. We'll keep it private.

...OR log in with your social account

...OR comment using your social account

Thanks for your comment! Keep it up!
We just need to have a quick look and it will be live soon.
The community is happy to hear your opinion! Keep contributing!